A union should be installed between the outlet of the air pressure maintenance device and the downstream isolation valve for servicing.
Air pressure maintenance device model d 2.
Where a field adjustable pressure reducing type air maintenance device is required to control the on off cycling of the systems air pressure as provided by an air compressor in dry pipe preaction type and dry pilot lines of deluge systems they shall be specifically listed for such use.
Globe s model h 1 air pressure maintenance device is an automatic field adjustable device of the pressure reducing type.
The viking model d 2 air pressure maintenance device is a pressure regulator that automatically reduces the supply air pressure to a preset requirement when connected to a constantly maintained air supply.
Model h 2 and h 3 air pressure maintenance device.
The h 1 is utilized in applications where there is a compressed air or nitrogen.
The amd 2 is rated for 175 psi.
Install the viking model d 2 air pressure maintenance device in the air or nitrogen supply piping between two valves to allow isolation of the device for maintenance and adjustment.